4-58
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
6) Set RTC Read to be always True (the time will not be written unless this point is
also True).
7) Set RTC Control elements Hours, Minutes and Seconds to be always True.
8) Use an external trigger to change RTC Write from False to True at the time you
have preset in step 3.
The time will now be set into Real Time Clock
Note: On the very first setting it will be necessary to program all the time elements
(Year, Month, Day etc)