5-42
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
<tagname>.CF
BOOL
Channel fault
TRUE: module diagnostics detect a fault in the
channel electronics or firmware (state = 7)
<tagname>.V
UINT
Voltage
Reports the channel voltage at the output
terminals, in units of millivolts and with an
accuracy of ± 500mV (††)
<tagname>.I
INT
Current
Reports the current for the channel in milliamps
and with an accuracy of ± 2mA and ± 10% of
measurement
<tagname>.STA
USINT
Channel state
Reports a state value for the channel:
1 = no vfield
2 = de-energized
3 = no load
4 = energized
5 = short-circuit
6 = field fault
7 = faulted
Note: (†) Discrepancy can only be reported TRUE when two modules are active in a
group. (††) The voltage element cannot report values below 0mV.