Rockwell-automation AADvance Controller Configuration Guide Manuel d'utilisateur Page 88

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 286
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 87
4-48
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
HART Passthrough
Direction: Appliction to the controller.
Type: BOOLEAN
Values:
TRUE = HART Passthrough is enabled and available for an Analogue Module.
FALSE = HART Passthrough is disabled and not available.
DEFAULT = FALSE
Description: Initiates the HART Passthrough feature to support HART messages on
the Analogue Input and Output Modules. The system will support messages on each
channel independently or in parallel
RTC Status Variables
The RTC status variables provide information about the controller real-time clock to
the application.
RTC Status: Year
Direction: input to application from controller
Type: word
Values:
2,000 to 2,399, or 0 (see description)
Description:
Reports the oldest value of real-time clock (RTC) year as voted by every 9110
processor module which is present and synchronized. Only updated if the real-time
clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).
RTC Status: Month
Direction: input to application from controller
Type: word
Values:
1 to 12, or 0 (see description)
Description:
Reports the oldest value of real-time clock (RTC) month as voted by every 9110
processor module which is present and synchronized. Only updated if the real-time
clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).
Vue de la page 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 285 286

Commentaires sur ces manuels

Pas de commentaire