Rockwell-automation AADvance Controller Configuration Guide Manuel d'utilisateur Page 78

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 286
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 77
4-38
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Status Integers
The variables in the rack of status integers provide information about the controller to
the application.
Number of Locked Input Variables
Direction: input to application from controller
Type: word
Values:
0 to 65,535
Description:
Reports the number of input variables that have been locked by the user. The upper
limit of 65,535 represents the capacity of the variable; in practice, the limit is the
number of variables in the application.
Number of Locked Output Variables
Direction: input to application from controller
Type: word
Values:
0 to 65,535
Description:
Reports the number of output variables that have been locked by the user. The upper
limit of 65,535 represents the capacity of the variable; in practice, the limit is the
number of variables in the application.
Processor Module A Temperature
Direction: input to application from controller
Type: word
Values:
0 to 65,535
Description:
Reports the temperature of the 9110 processor module in the given slot in degrees
centigrade. Set to 0 (zero) if no processor module is present.
Vue de la page 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 285 286

Commentaires sur ces manuels

Pas de commentaire