4-14
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
The following message now appears.
10) Click OK and another error message is displayed.
11) Click OK then Cancel to Exit ControlFLASH.
12) Reboot the processor module by switching the power OFF then ON and hold in
the Fault Reset button as the module reboots until the Aux LED goes amber.
The processor module(s) will reboot into the Recovery Mode indicated by the
following LED states on the processor module.
Healthy Green (dependent on Module health)
Ready Amber
Run Amber
System Health Green (dependent on system health)
Force Amber
Aux Amber
Stage 2: Installing the ControlFLASH Firmware Kit for OS, FPGA, LSP and BUSP
This procedure describes how to upgrade the Processor Firmware for OS, FPGA, LSP
and BUSP.
The procedure that follows is basically the same as for stage 1.
1) Run the 354400_102_ControlFLASH.msi file.
2) Click NEXT.
3) Read and agree the License.
Vue de la page 53