10-6
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Configure a Dual Network
1) To configure a redundant dual network select both networks when creating a
bound variable.
The variable will be sent over both physical networks, so if one network fails
the consumer will still receive the variable.
Redundant Physical and Logical Networks
1) Set up two networks connected to resources 1 & 2.
2) Configure the IP Addresses as follows:
SNCP_Workbench connection: IP Address 1 = 10.75.104.99, IP Address
1 10.75.104.100
SNCP_1 connection: IP Address 2 = 10.44.200.10, IP Address 2 =
10.44.200.20;
IP Address 3 = 10.44.210.10, IP Address 3 = 10.44.210.20