5) Click on the S1-1 row and set the required Inactivity and Idle values.
Inactivity values range from 1s minimum to 65535s maximum with a default
value of 600s. After this period, if no data has flowed in either direction, the
TCP connection will be closed.
Note: TCP connections are also subject to the keep-alive period.
Idle values range from 1ms minimum to a maximum of 1000ms with a default
value of 3ms. This is the time between characters arriving at the serial port
that defines when a "serial packet" has ended and should be passed on to TCP.
6) Click on the Apply button.
You have now enabled the TCI function.
7) To use TCI, the resource must be stopped.