Chapter 4
Configuring DriveLogix Motion
De-energizing the Drive to
Connect or Disconnect a
Cable
During the process of configuring DriveLogix motion you will need to
connect or disconnect a programming or network cable at the controller.
You should do this only if the drive is de-energized.
1. Turn off and lock out input power. Wait five minutes.
2. Verify that there is no voltage at the drive’s input power terminals.
3. Measure the DC bus voltage at the +DC & -DC terminals on the Power
Terminal Block. The voltage must be zero.
4. Connect or disconnect the programming or network cable.
5. Turn power back on and proceed with configuring DriveLogix motion.
About this Chapter
This chapter introduces DriveLogix5730 motion. The steps in this chapter
provide the minimum settings required to begin testing DriveLogix motion.
System Requirements
PowerFlex 700S Phase II Drive with firmware revision 2.XX or higher
DriveLogix5730 Controller with firmware revision 15.XX or higher
DriveExecutive programming software version 3.02 or higher
RSLogix 5000 programming software version 15 or higher
!
ATTENTION: Severe injury or death can result from electrical
shock or burn. Verify that the voltage on the bus capacitors has
discharged before connecting to the communication ports.
Measure the DC bus voltage at the +DC & -DC terminals on the
Power Terminal Block. The voltage must be zero.