Rockwell-automation 5730 DriveLogix5730 Controller for PowerFlex 700S Manuel d'utilisateur Page 111

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 217
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 110
Communicating with Devices on an EtherNet/IP Link 6-7
Using RSLogix 5000 Software to Set the IP Address
ahw0903.tif
ahw0904.tif
1. Create a new offline project, with the drive and any other necessary components.
2. In the Controller Organizer, select the I/O Configuration folder. Right-click the selected folder and select New Module.
3. Select a DriveLogix5730 Ethernet
Port from the list of possible
communication devices.
Click OK.
ahw0905.tif
4. Enter a Name for the port and the desired address.
Click Finish.
Important: You must create an offline project and download it to
the controller before going online. If the controller is
already programmed, skip these first three steps.
Note: The selected controller will verify that the IP address that has been
assigned in this dialog does not belong to another device on the network. If the
IP address exists, a warning message will display.
Vue de la page 110
1 2 ... 106 107 108 109 110 111 112 113 114 115 116 ... 216 217

Commentaires sur ces manuels

Pas de commentaire