2-10 Placing and Configuring the Drive
Table 2.E Mapping for User-Defined 2 Communication Format
For each of the communication formats, drive_module:O.LogicCommand
and drive_module:I.LogicStatus are provided as DINT data types. In
addition to these tags, the control bits for each are also available as Boolean
values with tag names that correspond to the control bits in the drive. This
gives you the option of programming the Logic Command and Status words
at the Boolean level or as an integer value.
Not all 32-bits within parameter 151 [Logic Command], are directly visible
in the PowerFlex 700S. To view all 32-bits, refer to parameter 152 [Applied
LogicCmd].
Controller Output Tag Element Drive Parameter Linked Parameter
LogicCommand 602 [FromDriveLogix00] 151 [Logic Command]
UserDefinedRealData[0] 603 [FromDriveLogix01] User Defined
UserDefinedRealData[1] 604 [FromDriveLogix02] User Defined
UserDefinedRealData[2] 605 [FromDriveLogix03] User Defined
UserDefinedRealData[3] 606 [FromDriveLogix04] User Defined
UserDefinedRealData[4] 607 [FromDriveLogix05] User Defined
UserDefinedRealData[5] 608 [FromDriveLogix06] User Defined
UserDefinedRealData[6] 609 [FromDriveLogix07] User Defined
UserDefinedRealData[7] 610 [FromDriveLogix08] User Defined
UserDefinedRealData[8] 611 [FromDriveLogix09] User Defined
UserDefinedRealData[9] 612 [FromDriveLogix10] User Defined
UserDefinedRealData[10] 613 [FromDriveLogix11] User Defined
UserDefinedIntegerData[0] 614 [FromDriveLogix12] User Defined
UserDefinedIntegerData[1] 615 [FromDriveLogix13] User Defined
UserDefinedIntegerData[2] 616 [FromDriveLogix14] User Defined
UserDefinedIntegerData[3] 617 [FromDriveLogix15] User Defined
UserDefinedIntegerData[4] 618 [FromDriveLogix16] User Defined
UserDefinedIntegerData[5] 619 [FromDriveLogix17] User Defined
UserDefinedIntegerData[6] 620 [FromDriveLogix18] User Defined
UserDefinedIntegerData[7] 621 [FromDriveLogix19] User Defined
UserDefinedIntegerData[8] 622 [FromDriveLogix20] User Defined
Controller Input Tag Element Drive Parameter Linked Parameter
LogicStatus 626 [To DriveLogix00] 155 [Logic Status]
UserDefinedRealData[0] 627 [To DriveLogix01] User Defined
UserDefinedRealData[1] 628 [To DriveLogix02] User Defined
UserDefinedRealData[2] 629 [To DriveLogix03] User Defined
UserDefinedRealData[3] 630 [To DriveLogix04] User Defined
UserDefinedRealData[4] 631 [To DriveLogix05] User Defined
UserDefinedRealData[5] 632 [To DriveLogix06] User Defined
UserDefinedRealData[6] 633 [To DriveLogix07] User Defined
UserDefinedRealData[7] 634 [To DriveLogix08] User Defined
UserDefinedRealData[8] 635 [To DriveLogix09] User Defined
UserDefinedRealData[9] 636 [To DriveLogix10] User Defined
UserDefinedIntegerData[0] 637 [To DriveLogix11] User Defined
UserDefinedIntegerData[1] 638 [To DriveLogix12] User Defined
UserDefinedIntegerData[2] 639 [To DriveLogix13] User Defined
UserDefinedIntegerData[3] 640 [To DriveLogix14] User Defined
UserDefinedIntegerData[4] 641 [To DriveLogix15] User Defined
UserDefinedIntegerData[5] 642 [To DriveLogix16] User Defined
UserDefinedIntegerData[6] 643 [To DriveLogix17] User Defined
UserDefinedIntegerData[7] 644 [To DriveLogix18] User Defined
UserDefinedIntegerData[8] 645 [To DriveLogix19] User Defined
UserDefinedIntegerData[9] 646 [To DriveLogix20] User Defined