2-22 Placing and Configuring the Drive
Configuring the Controller’s
Response to a Connection
Failure
You can configure the drive module to generate a major fault in the
controller if the drive loses its connection to the controller.
If you do not configure the major fault to occur, you should monitor the
drive module status. If the drive loses its connection to the controller:
Outputs remain in their last
Inputs remain in their last state
By default the drive will fault
Configure the drive to generate a controller major fault when the drive loses
its connection to the controller. Or, monitor the status of the drive module.
ahw0798.tif
Check this box to configure the drive
module to generate a major fault if it loses
its connection to the controller
!
ATTENTION: If a drive loses its connection to the controller,
the controller and other I/O modules continue to operate based
on old data from the drive, and the drive can continue to operate
based on old data from the controller. To avoid potential personal
injury and damage to machinery, make sure this does not create
unsafe operation.