50 Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 2 Installation and Wiring
ArmorConnect Connections
Figure 25 - ArmorConnect Receptacles
Factory-installed ArmorConnect gland plate connections
Figure 26 - ArmorConnect Connections
Control Power Receptacle
Three-Phase Power Receptacle
Control Power Receptacle
Three-Phase Power Receptacle
10 A Short Circuit Protection Rating 25 A Short Circuit Protection Rating
Table 4 - ArmorConnect Gland Plate Conductor Color Code
Terminal Designations Description Color Code
A1 (+) Control Power Input Blue
A2 (–) Control Power Common Black
A3 (+) Unswitched Control Power Red
PE Ground Green/Yellow
1/L1 Line Power – Phase A Black
2/L2 Line Power – Phase B White
3/L3 Line Power – Phase C Red