116 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Trip Status
This parameter provides trip
identification.
Parameter Number 4
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value 16383
Default Value 0
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X Short Circuit
—————————————— X Overload
————————————— X —— Phase Loss
———————————— X ——— Reserved
——————————— X ———— Reserved
—————————— X ————— Control Power
———————— X —————— I/O Fault
———————— X ——————— Over Temperature
——————— X ———————— Phase Imbalance
—————— X ————————— A3 Power Loss
————— X —————————— Reserved
———— X ——————————— Reserved
——— X ———————————— EEprom
—— X ————————————— HW Fault
X X ————————————— Reserved