122 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Produced Assembly Config Group
Bit
Warning
1514131211109876543210
—————————————— X
EEPROM Fault
—————————————— X Internal Comm
————————————— X —— Hardware Fault
———————————— X ———
Control Module
XXXXXXXXXXXX Reserved
Int00DeviceOut Cfg
This parameter is used to specify
Int00DeviceOut of produced assembly
150 or 151.
Parameter Number 13
Access Rule GET/SET
Data Type USINT
Group Produced Assembly Config
Units
Minimum Value 0
Maximum Value 108
Default Value 1
Int01DeviceOut Cfg
This parameter is used to specify
Int01DeviceOut of produced assembly
150 or 151.
Parameter Number 14
Access Rule GET/SET
Data Type USINT
Group Produced Assembly Config
Units
Minimum Value 0
Maximum Value 108
Default Value 4
Int02DeviceOut Cfg
This parameter is used to specify
Int02DeviceOut of produced assembly
150 or 151.
Parameter Number 15
Access Rule GET/SET
Data Type USINT
Group Produced Assembly Config
Units
Minimum Value 0
Maximum Value 108
Default Value 5