136 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Trip Status
This parameter provides trip
identification.
Parameter Number 4
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
Bit
Function
1514131211109876543210
——————————————— X Short Circuit
—————————————— X Overload
————————————— X —— Phase Short
———————————— X ——— Ground Fault
——————————— X ———— Stall
—————————— X ————— Control Power
————————— X —————— I/O Fault
———————— X ——————— Over Temperature
——————— X ———————— Over Current
—————— X ————————— A3 Power Loss
————— X —————————— Internal Comm
———— X ——————————— DC Bus Fault
——— X ———————————— EEprom
—— X ————————————— HW Fault
X —————————————— Restart Retries
X —————————————— Misc. Fault