Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 163
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Speed Reference
Valid Speed References for the
Bulletin 284E ArmorStart are the
following:
1 = Internal Freq
2 = Reserved
4 = Preset Freq
5 = Comm Port
6 = StpLogic
9 = Jog Freq
Parameter Number 138
Related Parameters
101, 102, 112, 139, 140,
151…154, 169, 170…177, 232,
240…247, and 250…257
Access Rule GET/SET
Data Type UINT
Group Drive Setup
Units
Minimum Value 0
Maximum Value 7
Default Value 5
Accel Time 1
Sets the rate of acceleration for all
speed increases.
Parameter Number 139
Related Parameters
138, 140, 151…154, 167,
170…177, and 240…247
Access Rule GET/SET
Data Type UINT
Group Drive Setup
Units 0.1 sec
Minimum Value 0.0 sec
Maximum Value 600.0 sec
Default Value 10.0 sec
Decel Time 1
Sets the rate of deceleration for all
speed decreases.
Parameter Number 140
Related Parameters
138, 139, 151…154, 168,
170…177, and 240…247
Access Rule GET/SET
Data Type UINT
Group Drive Setup
Units 0.1 sec
Minimum Value 0.1 sec
Maximum Value 600.0 sec
Default Value 10.0 sec
Maximum Freq
Accel Time
-------------------------------------- A c c e l R a t e=
Maximum Freq
Decel Time
-------------------------------------- D e c e l R a t e=