174 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Figure 71 - Overload Trip Curves
Maximum Voltage
Sets the highest voltage the drive will
output.
Parameter Number 188
Related Parameters 104, 185, 186, 187
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units 1V AC
Minimum Value 20V AC
Maximum Value Drive Rated Volts
Default Value Drive Rated Volts
Current Limit 1
Maximum output current allowed
before current limiting occurs
Parameter Number 189
Related Parameters 133, 218
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units 0.1 A
Minimum Value 0.1 A
Maximum Value Drive rated amps X 1.8
Default Value Drive rated amps X 1.5
Motor OL Select
Drive provides Class 10 motor
overload protection. Settings 0…2,
select the derating factor for I
2
t
overload function.
0 = No Derate
1 = Min. Derate
2 = Max. Derate
Parameter Number 190
Related Parameters 132, 133
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units 1
Minimum Value 0
Maximum Value 2
Default Value 0
0
0
20
40
60
80
100
25 50 75 100 125 150 175 200
% of P132 [Motor NP Hertz]
No Derate
% of P133 Motor OL Current
0
0
20
40
60
80
100
25 50 75 100 125 150 175 200
% of P132 [Motor NP Hertz]
Min Derate
% of P133 Motor OL Current
0
0
20
40
60
80
100
25 50 75 100 125 150 175 200
% of P132 [Motor NP Hertz]
Max Derate
% of P133 Motor OL Current