Rockwell-automation 284E ArmorStart with EtherNet/IP - User Manual Manuel d'utilisateur Page 296

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 348
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 295
296 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
The following common services are implemented for the Overload Object.
Device Level Ring (DLR)
Object
CLASS CODE 0x0047
The following class attributes will be supported for the DLR Object.
A single instance (Instance 1) will be supported with the following instance attributes.
Attribute ID Access Rule Name Data Type Value
3 Get/Set FLA Setting BOOL xxx.x amps
4 Get/Set Trip Class USINT
5 Get Average Current INT xxx.x amps
7 Get % Thermal Utilized USINT xxx% FLA
8 Get Current L1 INT
xxx.x amps9 Get Current L2 INT
10 Get Current L3 INT
190 Get/Set FLA Setting Times 10 BOOL xxx.xx amps
192 Get Average Current Times 10 UINT xxx.xx amps
193 Get Current L1 Times 10 UINT
xxx.xx amps194 Get Current L2 Times 10 UINT
195 Get Current L3 Times 10 UINT
Service Code
Implemented for:
Service NameClass Instance
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 2
Attribute ID Access Rule Name Data Type Value
1 Get Network Topology USINT 0 = Linear, 1 = Ring
2Get Network StatusUSINT 0 = Normal
1 = Ring Fault
2 = Unexpected Loop Detect
3 = Partial Network Fault
4 = Rapid Fault/Restore Cycle
10 Get Active Supervisor Address Struct of
UDINT
Array of 6
USINT
Ring Supervisor
12 Get Capability Flags DWORD 0x00000002
Vue de la page 295