Rockwell-automation 284E ArmorStart with EtherNet/IP - User Manual Manuel d'utilisateur Page 39

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 348
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 38
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 39
Installation and Wiring Chapter 2
24V DC Control Power
24V DC (–15%, +10%)
A1 = Switched +V
A2 = Common for both switched and unswitched (–V)
A3 = Unswitched +V
Input and Output Characteristics
5-pin female connectors (M12)
4 fixed inputs (two per connector) – software selectable sink or source
2 sourcing outputs DC (solid-state) – (one per connector)
Input and Output Power Connection
Sensor Power will be sourced from +24V supplied from A3(+) and A2(–).
Output power will be sourced from +24V supplied from A1(+) and A2(–).
Max. current per output point is 0.5 A and is not to exceed 1.0 A total
Vue de la page 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 347 348

Commentaires sur ces manuels

Pas de commentaire