Rockwell-automation IASIMP Computer Numerical Control (CNC) Machining Manuel d'utilisateur Page 265

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 278
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 264
Rockwell Automation Publication IASIMP-QS034A-EN-P - October 2012 265
Logix Communication and Controller Configuration Appendix D
Load the Controller Firmware
1. Apply input power to the CompactLogix controller power supply.
2. From the Tools menu,
select ControlFLASH.
The Welcome to
ControlFLASH dialog
box opens.
3. Click Next.
4. Select your controller
catalog number.
In this example, 1768-L43
is the controller catalog
number. The steps to
download other Logix
controller firmware are
similar.
5. Click Next.
TIP
This procedure shows how to load firmware in the controller by using a serial connection. It is faster to load the
firmware by using an EtherNet/IP connection. For details, see the controller installation instructions.
Vue de la page 264
1 2 ... 260 261 262 263 264 265 266 267 268 269 270 ... 277 278

Commentaires sur ces manuels

Pas de commentaire