72 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 4 No-load Test
2. In the Switch Method Selection dialog, press or .
3. If you select , the:
drive must be set to Local Control
position switch must be set to Drive
bypass contactor must be ON
drive must not be running.
4. If you select , the:
drive must be set to Local Control
position switch must be set to Drive
drive must be running.
5. Press to confirm selection.
ATTENTION: If the conditions are incorrect, the following dialog appears.