42 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 3 Commissioning
3. Press , and press in the Start Drive? dialog box to
confirm operation.
4. When the Actual Frequency reaches 10 Hz, press .
Press in the Accel Speed by Step? dialog box.
The Set Frequency and Actual Frequency are now 11 Hz.
IMPORTANT
When the drive is 0.5 Hz, the “Connect” light will be illuminated. When the
speed of the drive surpasses 0.5 Hz, the “Connect” and “Running” lights will be
red. The “Warning” light will illuminate when the Actual Frequency increases
above 10.00 Hz. This is an internal function for testing purposes only.
TIP
T Parameter T09 determines the value of the frequency step change. The
default is 1. Refer to Access T Parameters
on page 64.