52 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 3 Commissioning
6. Under Control Owner Selection, press .
7. Select to confirm selection in the Select Local Control?
dialog, and press to return to the Main Interface Screen and
confirm the Local status indicator is on.
Verify Operation of Input/Output and Bypass Isolation Switches
(Manual Bypass)
Input/Output Isolation Switches
1. Press from the Main Interface screen.