Rockwell-automation 6000 PowerFlex Medium Voltage Variable Frequency D Manuel d'utilisateur Page 49

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 98
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 48
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 49
Commissioning Chapter 3
3. Press and confirm the Power Module Cabinet Fan Fault.
4. Turn the (Q13) circuit breaker to the ON position, to remove the fault.
5. Press to return to the Main Interface Screen.
Simulate Cabinet Door Open Warning
1. Open the left Isolation Transformer Cabinet door.
2. Press to confirm the Cabinet Door Open Warning.
The drive will shut off.
3. Close the left Isolation Transformer Cabinet to remove the warning.
4. Repeat this procedure using the:
Right Isolation Transformer Cabinet door
Left Power Module/LV Cabinet door
Right Power Module/LV Cabinet door
Bypass Cabinet door (if applicable)