Rockwell-automation 1772-LP3 PLC - 2/30 Programmable Controller Progra Manuel d'utilisateur Page 48

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 346
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 47
Data Table
Chapter 3
321
The hardware-program interface is illustrated in Figure 3.7 by showing
the operational relationship between the input and output devices, the
input/output image table and the user program.
When an input device connected to terminal 113/12 is closed, the input
module circuitry senses a voltage. The On condition is reflected in the
input image table bit 113/12. During the program scan, the processor
examines bit 113/12 for an On (1) condition. If the bit is On (1), the
Examine On instruction is logically true. A true condition is displayed as
an intensified instruction. A path of logic continuity is established and
causes the rung to be true. The processor then sets output image table bit
012/06 to On (1). The processor turns on terminal 012/06 during the next
I/O scan and the output device wired to this terminal becomes energized.
When the rung condition is true, the output instruction is intensified.
3.3.3
Fundamental Operation
Vue de la page 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 345 346

Commentaires sur ces manuels

Pas de commentaire