Rockwell-automation 1772-LP3 PLC - 2/30 Programmable Controller Progra Manuel d'utilisateur Page 153

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 346
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 152
Output Override and I/O Update Instructions
Chapter 7
711
Fault zones can be programmed around certain parts of the program or the
entire program using fault status bits and MCR or ZCL zones. The fault
status bits used for remote fault zone programming are located in data table
words 125
8
and 126
8
(Table 7.B).
CAUTION: Input modules cannot be located in rack 2, module
groups 5 and 6 if words 125 and 126 are used for fault status
bits.
A group of four fault status bits corresponds to a single I/O rack
(Table 7.B). For example, bits 125/07
8
–125/04
8
correspond to rack 1, and
bits 125/03
8
–125/00
8
correspond to rack 2. Although bits 126/13
8
–126/10
8
are not used as fault status bits, they cannot be used for storage.
Table 7.B
Fault
Status Bits
I/O Rack Module Groups Fault Status Bit
1 0, 1
2, 3
4, 5
6, 7
125/07
125/06
125/05
125/04
2 0, 1
2, 3
4, 5
6, 7
125/03
125/02
125/01
125/00
3 0, 1
2, 3
4, 5
6, 7
125/17
125/16
125/15
125/14
4 0, 1
2, 3
4, 5
6, 7
125/13
125/12
125/11
125/10
5 0, 1
2, 3
4, 5
6, 7
126/07
126/06
126/05
126/04
6 0, 1
2, 3
4, 5
6, 7
126/03
126/02
126/01
126/00
7 0, 1
2, 3
4, 5
6, 7
126/17
126/16
126/15
126/14
Vue de la page 152
1 2 ... 148 149 150 151 152 153 154 155 156 157 158 ... 345 346

Commentaires sur ces manuels

Pas de commentaire