Sequencer Instructions
Chapter 15
158
Figure 15.6
SEQUENCER
OUTPUT Example Rung
SEQUENCER OUTPUT
COUNTER ADDR:
054
CURRENT STEP:
007
SEQ LENGTH:
009
WORDS PER STEP:
2
FILE: 600-621
MASK: 211-212
054
(EN)
17
054
(DN)
15
OUTPUT WORDS
1: 011
3:
2: 013
4:
||
14
114
When switch 114/14 closes, the Sequencer Output instruction increments
to step 008 and controls the 32 outputs corresponding to the specified
output words (less those output that are masked). The control of the output
terminals will be in accordance with the data stored in step 008 of the
sequencer table and mask conditions as shown in Figure 15.7.
Figure 15.7
Control
of Sequencer Outputs
0 1 1 0 0 1 0 1 1 0 0 1 0 1 1 0 1 1 1 0 1 1 0 0 1 0 0 1 1 0 1 0
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0
0 1 1 0 0 1 0 1 1 0 0 1 0 1 1 0 1 1 1 0 1 1 0 0 1 0 NOTE
1716151413121110070605040302010017161514131211100706050403020100
Bit
Numbers
Sequencer T
able, Step 008
Mask Words
Mask Conditions
Output Status
Output Modules
1
211 212
01
1Slot 1
01
1Slot 0
013Slot 1 013Slot 0
NOTE:
Masking excludes these outputs from the sequencer operation. They can be
controlled by other instructions in user program.
The procedure for using the data monitor mode to monitor, load or edit file
data is presented in Chapter 12. It may be necessary to use the data monitor
mode to set the mask word bits in order for the instruction to operate. It
may also be necessary to load data into the sequencer table.
The binary data monitor display for a Sequencer Output instruction with 9
steps and 2 words per step is shown in Figure 15.8. Differences between