Addressing
Appendix A
A9
Figure A.6
Illustration
of 1slot Addressing with 16point I/O Modules
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
Input
Terminals
Output
Terminals
171615140403020100
Output
image table word
corresponding to the I/O group.
1slot
I/O Group
171615140403020100
Output image table word
corresponding to the I/O group.
171615140403020100
Input image table word
corresponding to the I/O group.
171615140403020100
Input image table word
corresponding to the I/O group.
1slot
I/O Group
OR
The
corresponding opposite image table word is not used
when 16-point modules are used.
Assigning I/O Rack Numbers
When you select 1-slot addressing, each slot is an I/O group. You still
assign one I/O rack number to eight I/O groups; therefore, in a 16-slot I/O
chassis you now have two I/O racks (Figure A.7).