Function Block Library 4–27
1336 FORCE — 5.9 August 1995
FUNCTION
Denominator = 1/2 × t × 1/(divisor gain) = 25600
where: t = a task interval of .020 seconds = 1/50 samples/second.
divisor gain = 256.
1. If Set = true, accumulator = Preset × denominator.
2. If Set = false,
accumulator = [Gain × (Input
i–1
+ Input)] +
previous accumulated value.
3. If accumulator ÷ denominator > Max,
Output = Max, Hi Lim = true, Lo Lim = false.
4. If accumulator ÷ denominator < Min,
Output = Min, Hi Lim = false, Lo Lim = true.
5. If accumulator ÷ denominator < Max and > Min,
Output = accumulator ÷ denominator, Hi Lim = false,
Lo Lim = false.
PARAMETERS DATA TYPE LINKABLE DEFAULT VALUE RANGE
Input Signed Integer Yes 0
±32767
Set Logic Input Yes False True/False
Preset Signed Integer Yes 0
±32767
Gain Signed Integer No 256
±16383
Min Signed Integer No 0 0 to –32767
Max Signed Integer No 0 0 to +32767
Lo Lim Logic Output No True/False
Hi Lim Logic Output No True/False
Output Signed Integer No
±32767
Example 1 — Gain = 256 = 1× — Horizontal Scale = 500mS/Division
Y
INTEGRATOR Output
+32767 "
32767 "
INTEGRATOR Input
B
In Example 1, the INTEGRATOR Output accumulates at a rate of 32767 units-per-second,
an amount equal to it’s constant INTEGRATOR Input level. It takes (2) seconds to traverse
the entire range.