Rockwell-automation 1336T Function Block Prog. Manual, Series A/B Manuel d'utilisateur Page 111

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 180
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 110
Function Block Library 4–49
1336 FORCE — 5.9 August 1995
SUB
BLOCK TYPE 27
decimal
1B
hexadecimal
Subtract
ID = Exec =
Output
NODE 0
In 1
NODE 1
Sub
NODE 2
DEFINITION
Subtracts two signed integers. Output will be clamped to ±32767
and not allowed to over or under flow.
INPUTS
In 1 — A signed integer between ±32767.
Sub — A signed integer between ±32767.
OUTPUT
Output — A signed integer between ±32767.
FUNCTION
Output = In 1Sub.
PARAMETERS DATA TYPE LINKABLE DEFAULT VALUE RANGE
In 1 Signed Integer Yes 0
±32767
Sub Signed Integer Yes 0
±32767
Output Signed Integer No
±32767
EXAMPLES EXAMPLE 1 EXAMPLE 2 EXAMPLE 3
In 1 +10 32765 –5
Sub +15 +2 –23
Output –5 32767 +18