Function Block Library 4–45
1336 FORCE — 5.9 August 1995
PARAMETERS DATA TYPE LINKABLE DEFAULT VALUE RANGE
Lim In Signed Integer Yes 0
±32767
Lim Set Logic Input Yes 0 True/False
Lim Data Signed Integer Yes 0
±32767
Lim Rate Unsigned Integer No 0
0 to 65535
Lim @ Lim Logic Output No True/False
Lim Out Signed Integer No
±32767
Lim @Lim = True
Time
Example 1
+ 32767
0
– 32767
Lim @Lim = False
When Lim Rate = 65535, t1 = 1 sec
When Lim Rate = 32767, t1 = 2 sec
Lim In
Lim Out
t1
RATE LIMITER
(continued)