1–21Getting Started
1336 FORCE — 5.9 August 1995
Step 5 — View Node Values
Drive analog outputs can be linked to function block nodes. Analog
scale factors can be set and the analog outputs can be linked to the
function block nodes by using the same block transfer routine. A
device such as an oscilloscope can be connected to the analog
outputs to monitor the operation of the function block program.
Set the Analog Output 1 Scale Factor and
Download to Drive
BTW
Data File
N57:0
4
8301 191 800 0 0 0 0 0 0
0 1 2 3 4 5 6 7 8 9
Words N57:2 contains the parameter number in hexadecimal format. Word
N57:3 contains the desired value in hexadecimal.
1. Set the Analog Output 1 Scale Factor (Parameter 401) to a value
of 2048.
2. Toggle bit I:00/00 to initiate the block transfer routine which
processes all function block links.
3. Verify that the write was successful. If N57:101 = 0301
hex
(Block
Transfer Read data), there are no errors.
Set the Analog Output 3 Scale Factor and
Download to Drive
BTW
Data File
N57:0
4 8301 195 800 0 0 0 0 0 0
0 1 2 3 4 5 6 7 8 9
1. Set the Analog Output 3 Scale Factor (Parameter 405) to a value
of 2048.
2. Toggle bit I:00/00 to initiate the block transfer routine which
processes all function block links.
3. Verify that the write was successful. If N57:101 = 0301
hex
(Block
Transfer Read data), there are no errors.