70 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 3 Product Commissioning
Using the
Rockwell Automation
BootP/DHCP Utility
The Rockwell Automation BootP/DHCP utility is a stand alone program that
incorporates the functionality of standard BootP/DHCP software with a user
friendly graphical interface. It is located in the Utils directory on the
RSLogix 5000 installation CD. The ArmorStart LT must have DHCP
enabled (factory default) to use the utility.
To configure your adapter using the BootP/DHCP utility, perform the following
steps:
1. Run the BootP/DHCP software.
In the BOOTP/DHCP Request History panel you will see the Ethernet
(Mac) addresses of the devices issuing requests.
Note: the Ethernet (Mac) address for a device can be found
on the product label.
Figure 41 - BOOTP/DHCP Request History Panel
2. Double-click the Ethernet (Mac) address of the device you want
to configure.
You will see the New Entry dialog with the device’s Ethernet Address
(MAC).
Figure 42 - New Entry Dialog Box