Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 113
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
Bit
Function
1514131211109876543210
—————————————— X
OverloadTrip
—————————————— X PhaseLossTrip
————————————— X —— UnderPowerTrip
———————————— X ———
SensorShortTrip
——————————— X ———— PhaseImbalanceTrip
—————————— X ————— NonVolMemoryTrip
————————— X —————— Reserved
———————— X —————— JamTrip
——————— X ———————— StallTrip
—————— X —————————
UnderloadTrip
——— X X X —————————— Reserved
—— X ————————————— OutputShortTrip
X —————————————— UserDefinedTrip
X ———————————————
HardwareFltTrip
The highlighted functions are enabled by default.
WarningStatus
This parameter provides the current
warning condition.
Parameter Number 43
Access Rule GET
Data Type WORD
Group Trip Status
Units
Minimum Value 0
Maximum Value 0xC295
Default Value