10–19Diagnostic Status Information
Publication
17706.5.16 - October 1996
1785KE Status Bytes
Bytes Bits Contents Description
1 all Operating status of PLC processor. For the 1785KE, this byte is always 0.
2
0 - 3
Type of interface module and processor
E = Check interface module expansion byte (byte3)
4 - 7
F = Computer
3 all Interface Module Expansion Byte 19 = 1785KE
4 all 00 = not used
5 - 6 all This is a pointer to the Active Node
Table
low byte first.
7 - 8 all This is a pointer to diagnostic counters low byte first.
9
0 - 4
Series and revision level of the module
0 = Revision A
1 = Revision B, etc.
5 - 7 0 = Series A
1 = Series B, etc.
10
0 - 1
Settings of the option switched on the
0 = 57,600 bits per second Data Highway Plus baud rate
2
module
DSR
3 - 7 Option Switch Settings; bit set to 0 is ON