9–11Diagnostic Counters
Publication
17706.5.16 - October 1996
1770KF2 and 1785KE DH+ and Asynchronous Link Diagnostic
Counters
This counter byte Counts the number of
0 Times received ACK with bad CRC.
1 Times timeout expired with no ACK received.
2 Transmit retries exhausted.
3 NAK/illegal protocol operation received.
4 NAK/bad LSAP received.
5 NAK/no memory received.
6 Received ACK/NAK too short.
7 Received ACK/NAK too long
8 Something other than an ACK/NAK received.
9 Token pass timeouts.
10 Token pass retries exhausted.
11 Claim token sequence entered.
12 Tokens claimed.
13 Bad CRCs in received frame.
14 NAK/illegal protocol operations sent.
15 NAK/bad LSAPs sent.
16 NAK/no memory sent.
17 Received frame too small.
18 Received frame too long.
19 Received a retransmission of a frame.
20 Received frame aborted (line noise).
21, 22 Messages successfully sent (low byte first).
23, 24 Messages successfully received (low byte first).
25, 26 Commands successfully sent (low byte first).
27, 28 Replies successfully received (low byte first).
29, 30 Commands successfully received (low byte first).
31, 32 Replies successfully sent (low byte first).
33 Replies could not be sent.
34 Active nodes.