9–6 Diagnostic Counters
Publication
17706.5.16 - October 1996
1747L541, L542, and L543 (SLC 5/03 and SLC 5/04 processors)
DF1 Diagnostic Counters
This counter byte Counts the number of
0, 1
RS232 modem line status:
Bit 0 = CTS input line status
Bit 1 = RTS output line status
Bit 2 = DSR input line status
Bit 3 = DCD input line status
Bit 4 = DTR output line status
2, 3 Total message packets sent
4, 5 Total message packets received
6, 7 Undelivered message packets
8, 9 Message packets retried
10, 11 Normal station poll list last scan time (100 ms increments)
12, 13 Normal station poll list maximum scan time (100 ms increments)
14, 15 Nonresponse due to bad message packets detected
16, 17 Unused
18, 19 Duplicate message packets received
20, 21 Priority station poll list last scan time (100 ms increments)
22, 23 DCD recovery field (times DCD toggled off and on)
24, 25 Lost modem field (times modem has been disconnected)
26, 27 Priority station poll list maximum scan time (100 ms increments)