1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-15
Valid Output Data Word Formats/Ranges
The analog output data received at the module is converted to
RAW/proportional data format. Unlike the 1769-IF4 and 1769OF2.
on-board scaling is not provided by the module. You must do this via
your control program.
The following table shows the valid output data format for the data
range provided by the module.
Table 4.10 Valid Output Data
Output Range Output Value Example Data Output Range
Condition
Raw/Proportional Data
Decimal Range
0 to 10V dc Over +10.5V dc N/A
N/A
(1)
(1) The module’s maximum range is 10.5V or 21 mA. An over-range flag is set at either value. This flag automatically resets when the output data is below the over-range
value.
N/A
+10.5V dc + 10.5V dc
Over-range
(1)
32640
0.0V dc to
+10.0V dc
+10.0V dc Normal 31104
+5.0V dc Normal 15488
0.0V dc Normal 0
0 to 20mA Over 21.0 mA N/A
N/A
(1)
N/A
21.0 mA 21.0 mA
Over-range
(1)
32640
0.0 mA to 20.0 mA 20.0 mA Normal 31104
10.0 mA Normal 15488
0.0 mA Normal 0