Publication 1769-UM008A-EN-P - November 2001
Quick Start for Experienced Users 2-5
The 1769-IF4XOF2 module is configured for current or voltage
operation by proper wiring of the analog I/O device to the module.
However, a channel is enabled using its configuration file.
The configuration file is typically modified using the programming
software configuration screen. It can also be modified through the
control program, if supported by the controller. See the configuration
file chart on page 4-8.
For an example of module configuration using MicroLogix 1500 and
RSLogix 500, see Appendix B. For an example of module
configuration using CompactLogix and RSLogix 5000, see Appendix C.
Step 5:
Configure the module
Reference
Chapter 4
(Module Data, Status, and
Configuration Channel for
1769-IF4XOF2)
Table 2.1 Configuration Data File
Word
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0
Not Used
(1)
EI3 EI2 EI1 EI0
FM0
(2)
PM0
(2)
Not
Used
(1)
PFE0
(2)
1
Not Used
(1)
EO1 EO0
FM1
(2)
PM1
(2)
Not
Used
(1)
PFE1
(2)
2SGN
Channel 0 Fault Value
(2)
0000000
3SGN
Channel 0 Program (Idle) Value
(2)
0000000
4SGN
Channel 1 Fault Value
(2)
0000000
5SGN
Channel 1 Program (Idle) Value
(2)
0000000
(1) Any attempt to write a non-valid (1’s) bit configurations into any not used selection field results in a module configuration er ror.
(2) Not all controllers support these functions. Refer to your controller’s user manual for details.