Publication 1761-UM006E-EN-P - August 2005
BOOTP Configuration Method (default) B-3
Using the Rockwell
BOOTP/DHCP Utility
The Rockwell BOOTP/DHCP utility is a standalone program that
incorporates the functionality of standard BOOTP software with a
user-friendly graphical interface. It is located in the Utils directory on
the RSLogix 5000 installation CD. It can also be downloaded from
www.ab.com/networks/bootp/index.html web page. The device
must have BOOTP enabled (factory default) to use the utility.
To configure your device using the BOOTP utility, perform the
following steps:
1. Run the BOOTP software. In the BOOTP Request History
panel you will see the hardware addresses of devices issuing
BOOTP requests.
2. Double-click on the hardware address of the device you want to
configure. You will see the New Entry pop-up window with the
device's Ethernet Address (MAC).