Publication 1761-UM006E-EN-P - August 2005
8-12 Connecting CompactLogix Controllers on Ethernet
The Message Instructions for the CompactLogix controller, Rungs 2
through 8, used to configure the ENI/ENIW module, must be “PLC2
Unprotected Write” Message Type. The “Destination Element” can be
any valid PLC2 command value. “010” is used in this example because
it is the first available value that the software will allow. This
parameter is not used by the ENI/ENIW, but must be a valid value for
RSLogix 5000 to accept it.
An example of the MSG Configuration tab and the Communication tab
for the MSG instruction used to configure the IP address for the
ENI/ENIW (Rung 4) are as follows:
Figure 8.12 ENI #2 Configuration - Message Configuration Tab