1 Publication 1746-6.1.2 - July 2000
Appendix
D
Wiring Without the Termination Panel
Overview
This appendix covers how to wire your SLC Servo Module without a
termination panel and includes the following topics:
Using fast inputs and outputs
Distances to user devices
Wiring your hardware
If you don’t use a termination panel, you must wire from the
connectors on the SLC Servo Module to these user devices:
Fast inputs and outputs
Estop Reset push-button, Estop string, and Estop relay
Power supplies
Encoders
Drives
Using Fast Inputs and
Outputs
When using fast inputs you must snub all inductive and capacitive
loads.
The high-level, on
state output
current:
is:
Maximum
(each output)
+5V @
±20.0 mA
Minimum
(each output)
+0V @
±20.0 mA
ATTENTION
!
To avoid damage to your equipment, do not
overload a 5V fast output circuit by wiring it for 24V.