3-24 Configuring the WIM
By default, when communications are disrupted (for example, loss of
wireless communication), the WIM and connected drive respond by
faulting. You can configure a different response to communication
disruptions using Parameter 07 - [Comm Flt Action].
To change the fault action
Set the value of Parameter 07 - [Comm Flt Action] to the desired
response:
Changes to this parameter take effect immediately. A reset is not
required.
Setting the Fault Action
!
ATTENTION: Risk of injury or equipment damage exists.
Parameter 07 - [Comm Flt Action] lets you determine the action of
the WIM and connected drive if communications are disrupted. By
default, this parameter faults the drive. You can set this parameter so
that the drive continues to run. Precautions should be taken to ensure
that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, disruption
of wireless communication).
Value Action Description
0 Fault The drive will fault.
1 Stop The drive will stop and not fault.
2 Zero data The drive is sent 0 for output data after a communications
disruption. This does not command a stop.
3 Hold last The drive continues in its present state after a communications
disruption.