10.4.1 Input
P
arameters for the Array Shift Up Instruction
This table lists the inputs for the ASU instruction and the variable type and data
type/range that each input supports.
Parameter
Description V
ariable T
ype Data/Type Range
EN While this input is true, the instruction executes. When
this input is false, the instruction does not execute.
Connect a Boolean input or output.
In Enter the name of a variable or a constant that you want
to move into the last element position of the array.
If no value is specified, 0 is used.
D simple
D constant
D element of an array
D integer
D double integer
D timer
(name.TPreset and
name.Elapsed)
D counter
(name.CPreset
and name.Current)
Array Enter the name of the array variable that you want to
use.
array D integer
D double integer