62 Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Chapter 4 Parameters and Function Codes
P443 Upper Limit Of Current Compensation Input Deadband 0 ON -16384 32767
P444 Lower Limit Of Current Compensation Input Deadband 0 ON -16384 32767
P445 Proportional Coefficient Of Current Compensation (%) 5 ON 0 199.99
P446 Integral Coefficient Of Current Compensation (ms) 100 ON 0 32767
P447 Lower Limit Of Current Compensation Output -100 ON -100 0
P448 Minimum Frequency For Current Compensation 5 ON 0 100
P449 Proportional Coefficient Of Current Compensation
Output (%)
0.99 ON 0 199.99
P450 Upper Limit Of Frequency Compensation Output 100 ON 0 100
P451 Low Speed Voltage Compensation (%) 0.99 OFF 0 10
P452 Low Speed Voltage Compensation Frequency Threshold 20 ON 0 100
P453 V/F Curve
0: Linear
1: Parabolic Curve
2: Predefined Curve #1
3: Predefined Curve #2
1OFF03
P454 Flux Time (s) 0.5 OFF 0 10
P455 Modulation Index 87.99 ON 0 199.99
P456 Motor Voltage Upper Limit 87.99 ON 0 199.99
P457 Flying Start Voltage Recovery Time (s) (Low Speed
Region)
5 ON 0 163.84
P458 Coefficient A 40 OFF 0 100
P459 Flying Start Voltage Recovery Time (s) (High Speed
Region)
5 ON 0 163.84
P460 Rated Output Frequency 50 OFF 0 75
P461 Restart Enable 0 ON 0 1
P462 Fault Reset Timeout (s) 120 ON 0 120
P463 Flying Start Low/High Speed Regions Boundary (%) 16 ON 0 100
P465 Power Cell Fault Auto Reset Delay (s) 4 ON 0 10
P466 Maximum Output Frequency 50 OFF 0 75
P467 Over Speed Enable 0 OFF 0 1
P470 Version Compatibility Enable 1 OFF 0 1
P497 Major Rev # Of DSP Main Firmware 0 Cannot
Modify
—— ——
P498 Minor Rev # Of DSP Main Firmware 2 Cannot
Modify
—— ——
P499 Display Fault Masks Button 0 ON 0 1
P500 Display DSP Variables 0 ON 0 1
Parameter
Number
Description Default
Value
Modify
Root
Lower
Limit
Upper
Limit