Rockwell-automation 6012DB PowerFlex Medium Voltage Variable Frequency Manuel d'utilisateur Page 59

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 138
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 58
Rockwell Automation Publication 6000-UM001B-EN-P - October 2014 59
Parameters and Function Codes Chapter 4
P232 Filter Time For Overspeed Fault (Lower Limit) 100 ON 0 32767
P233 Threshold Of Over-Speed Fault At Lower Frequency Limit 20 ON 0 199.99
P234 Threshold Of Over-Speed Fault At Upper Frequency Limit 20 ON 0 199.99
P235 Frequency Deviation Warning Cancellation Threshold 0.99 ON 0 199.99
P236 Frequency Deviation Warning Threshold 6 ON 0 199.99
P237 Frequency Deviation Warning Delay (ms) 8 ON 0 32767
P238 Motor Stall Fault Threshold 10 ON 0 199.99
P239 Motor Stall Fault Delay (ms) 6000 ON 0 32767
P240 Transformer Over Temperature Fault Delay (ms) 5000 ON 0 32767
P241 Transformer Over Temperature Warning Delay (ms) 5000 ON 0 32767
P247 Software Interlock: 1-Disable, 0-Enable 1 ON 0 1
P250 Input Contactor/Circuit Breaker Close Delay (ms) 5000 ON 0 10000
P251 Frequency Command-Low Frequency Region Boundary 0.5 ON 0 100
P252 Motor In Stopping Condition Threshold 1 ON 0 100
P253 Motor Coast Stop Time 10 ON 0 10000
P256 Ground Fault Warning Cancellation Threshold 10 ON 0 199.99
P257 Motor Stall Warning Cancellation Threshold 2.98 ON 0 199.99
P259 Frequency Command Analog Offset 0 ON -100 199.99
P260 Frequency Command Analog Scaling Factor 100 ON 0 199.99
P261 Frequency Command Analog Minimum 0.49 ON 0 199.99
P262 Frequency Command Source Selection: 0-Digital, 1-
Analog
0OFF01
P270 Delayed Lockout Time Of Stop Operation (ms) 2000 ON 0 5000
P271 Flux Delay (ms) 50 ON 0 5000
P300 Digital Output #0 Memory Address 99 ON 0 500
P301 Digital Output #0 Logic: 1-Inverting, 0-Non-Inverting 0 ON 0 1
P302 Digital Output #0 Bit Selection (0...15) 0 ON 0 15
P303 Digital Output #0 Delay (ms) 0 ON 0 32767
P304 Digital Output #1 Memory Address 99 ON 0 500
P305 Digital Output #1 Logic: 1-Inverting, 0-Non-Inverting 0 ON 0 1
P306 Digital Output #1 Bit Selection (0...15) 1 ON 0 15
P307 Digital Output #1 Delay (ms) 0 ON 0 32767
P308 Digital Output #2 Memory Address 99 ON 0 500
P309 Digital Output #2 Logic
1: Inverting
0: Non-Inverting
0ON01
P310 Digital Output #2 Bit Selection (0...15) 2 ON 0 15
P311 Digital Output #2 Delay (ms) 0 ON 0 32767
P312 Digital Output #3 Memory Address 99 ON 0 500
Parameter
Number
Description Default
Value
Modify
Root
Lower
Limit
Upper
Limit