112 Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Chapter 5 Preventative Maintenance and Component Replacement
1. Disconnect the data cable from communication board, the EtherNet/IP
cable from PLC, the ground cable, and the 24V power supply cable.
2. Remove and retain four screws from HMI.
3. Install the new HMI from the inside of the LV Control Cabinet door.
4. Reconnect all cables in reverse order of removal.
Data Cable from
Communication Board
EtherNet/IP Cable from PLC
Ground Cable
24V Power Supply
HMI
IMPORTANT
Support the HMI from the outside of the door to prevent it from falling through
the front of the door.
HMI Hardware
TIP
The following HMI components can be replaced:
Logic Module
Display Module
Bezel
Backlight
Battery
See publication 2711P-UM006_-EN-P
for further information.