Rockwell-automation 284E ArmorStart EtherNet IP Communications and Con Manuel d'utilisateur Page 45

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 90
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 44
Rockwell Automation Publication 280E-PM001A-EN-P – August 2011 45
ArmorStart
®
EtherNet/IP
Communications & Control Programming Manual Chapter 4
6. To i d e n ti f y w h a t f au l t o c c ur r e d :
a. Double click on Controller Tags at the top of the Controller
Organizer
b. Verify that a fault occurred within the unit by looking at the
Tr ipPr e s e nt tag within AS_EIP_280:I. Expand AS_EIP_280:I by
clicking on the plus sign next to AS_EIP_280:I. The Tr i pPr es ent bit
should be a 1.
c. To see which fault occurred, expand AS_EIP_280:I and scroll down
and expand AS_EIP_280:I.Int01DeviceOut to see the individual bits
of this word. AS_EIP_280:I.Int01DeviceOut points to parameter 4
which is Tr ip St a tu s . These 16 bits correlate to the Tr ip S ta t us bit
description in the Bulletin 280E Trip Status
section on page 71.
d. Compare the bits of AS_EIP_280:I.Int01DeviceOut to the Trip Status
definition in the Bulletin 280E Trip Status
section on page 71. Verify
the reported fault matches the fault that was created.