Rockwell-automation 284E ArmorStart EtherNet IP Communications and Con Manuel d'utilisateur Page 13

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 90
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 12
Rockwell Automation Publication 280E-PM001A-EN-P – August 2011 13
ArmorStart
®
EtherNet/IP
Communications & Control Programming Manual Chapter 2
Connection Tab
Click on the Connection tab to display the following:
The Request Packet Interval (RPI) indicates the maximum frequency at which
data will be received. It is possible that data could come more quickly than the
time interval assigned in the RPI. In the majority of cases, the default 20 ms
should be the optimal setting. If you check the Inhibit Module option,
connection to controller tags will be broken. The Major Fault on Controller if
Connection Fails While in Run Mode option should be checked to ensure that
the controller processes the connection fault with the ArmorStart. The Use
Unicast Connection over EtherNet/IP is checked to use the Unicast mode
instead of the EtherNet/IP mode. This appears only for modules using
RSLogix 5000 software version 18 or later which supports Unicast.
Vue de la page 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 89 90

Commentaires sur ces manuels

Pas de commentaire