15-2 Upgrading the Operating System
The MicroView Opening Menu Appears.
6. Highlight Upgrade Operating System and press [Return].
The Communication Port Selection screen appears. You will not
see this prompt if a communication port was specified during
the installation of the software.
7. Highlight the serial port on your computer that is connected to
the MicroView (COMM 1 or COMM 2) and press [Return].
The DPS software establishes a communications link with the
MicroView. If a communication link does not occur in 90
seconds you will get an error message. Check the Mode setting
and cable connections.
8. A message is displayed indicating the Operating System in the
MicroView and the Operating System of the application file. For
example:
MicroLogix DF1 application file is
resident in your MicroView.
MicroLogix DF1 Operating System will
be downloaded.
PRESS Y to continue.
PRESS N to abort.